Typical Installation Schematics
The following section includes typical schematics of how a heat pump can be connected. Only the load side is shown i.e. the heating distribution system. It is important to note that the schematics are only general arrangements and hence do not illustrate all required valves or fittings. They are only a guide and should not be used as full installation plans.
Domestic heat pump with underfloor (single manifold)
Kensa Compact heat pumps have inbuilt water pumps for both the ground and the heating distribution circuits. The water pump for the heating distribution circuit is sufficient to provide enough flow and pressure for underfloor distribution systems comprising of a single manifold. Additional pumps should not be required.
Buffer tanks are not required if 25% of the underfloor zones are left hydraulically open. These open zones are generally areas such as halls and bathrooms.
Thermal mixing valves should be removed from the underfloor manifold if fitted.
Kensa would always recommend that an expansion vessel is fitted on the heating distribution circuit
Domestic heat pump with underfloor (more than one manifold)
Due to the pressure and flow requirements of the underfloor distribution circuits each individual manifold should have a small circulating pump fitted. The integral heating distribution pump in the heat pump circulates water around a shunt loop (ring main). Each underfloor manifold pump then draws water as required from the shunt loop.
Buffer tanks are not required if 25% of the underfloor zones are left hydraulically open. These open zones are generally areas such as halls and bathrooms.
Thermal mixing valves should be removed from the underfloor manifold if fitted.
Kensa would always recommend that an expansion vessel is fitted on the heating distribution circuit.
Domestic heat pump with underfloor systems (fully controlled zones)

For heating distribution systems, which require each zone to be fully controlled, Kensa would recommend fitting a two connection buffer vessel. This will avoid any short cycling problems that could occur at low load conditions.
Thermal mixing valves should be removed from the underfloor manifold if fitted.
Kensa would always recommend that an expansion vessel is fitted on the heating distribution circuit.
Domestic heat pump with radiators.

When operated with radiators to avoid short circulating problems, one radiator (the bypass radiator) should be left ‘open’, i.e. any TRV is removed. This radiator can be positioned in areas such as halls or bathroom.
Kensa would always recommend that an expansion vessel is fitted on the heating distribution circuit.
Domestic heat pump with domestic hot water via an indirect tank.

Under normal conditions the heat pump will provide heat for the underfloor distribution system at an ideal temperature of 35C.
When there is a demand for DHW the three-port valve diverts the flow from the underfloor distribution circuit into the indirect coil. The temperature of the water from the heat pump is raised to approximately 50C.
When the required temperature is reached within the tank, the three port valve switches back to the underfloor distribution and the temperature drops back to 35C.
If this scheme is being considered, please contact Kensa for additional details.
For other configurations or further details please contact Kensa Technical Department.